施耐德-71911-Flusarc-36_Op_Main(EN) 1、Use of the T1 function (contd.) Closing the switch disconnector ■ Act on the interlock, by shifting it downwards ■ Insert the operating lever into the switch disconnector control. ■ Grasp the lever with both hands. ■ Turn the lever clockwise, up to reach the end of stroke The mimic diagram indicator will turn from the open line position to the closed line position . ■ Extract the operating lever. 2、pening the switch disconnector ■ Insert the operating lever into the switch disconnector control ■ Grasp the lever with both hands ■ Turn the lever counter clockwise, up to reach the end of stroke The mimic diagram indicator will turn from the closed line position to the open line position ■ Extract the operating lever 3、Maintenance (contd.) ■ Ensure that the function’s earthing switch is closed ■ Act on the interlock of the door, by shifting it rightwards ■ After unlocking the fuse compartment door handle by the key, rotate the handle itself counter clockwise ■ Fully open the fuses compartment door, in order to restore the correct position of the rod placed on the fuses compartment door ■ Apply the lever to the fuseholder cover and screw into the two holes predisposed on the cover the two finned screws.